Physics-Based Simulation
Generated using TESPy rather than physical testbed measurements. Network components and operating conditions can be modified.
A reproducible simulation benchmark for virtual sensing, graph learning and physics-based information augmentation in district heating networks.
EPFL IMOS Lab · Swiss Federal Institute of Metrology (METAS)

A steady-state district heating simulation driven by weather-dependent consumer demand, designed to support reproducible research on computational sensing.
Generated using TESPy rather than physical testbed measurements. Network components and operating conditions can be modified.
Mass flow, pressure and temperature signals characterize the coupled thermal and hydraulic system.
Estimate pressure and temperature from mass flow measurements and component characteristics.
Four consumers are connected through feed and return pipes, a heat source, pump, valves and junctions. Supply and return water temperatures span approximately 50–90 °C and pressures 3–5 bar.

The published simulator allows researchers to adapt network topology and component characteristics. The original study uses weather-dependent demand over a year, evaluated through hourly steady-state solutions.
Download the original files from the research repository.
| File | Content | Size | Access |
|---|---|---|---|
df_sensors.csv | Simulated sensor readings | 4.37 MB | Raw file ↗ |
df_physics.csv | Physics-related variables | 2.14 MB | Raw file ↗ |
DHN_Topology_TESPY.py | Customizable TESPy simulator | 10.6 KB | Raw file ↗ |
Explore simulated sensor readings or physics-derived signals. Compare compatible variables, inspect individual samples and zoom into the hourly time series. Files stay in your browser.
| Signal | Min | Max | Mean | Negative | Zero | Valid |
|---|
Elapsed time is reconstructed from the hourly sample spacing in the original dataset. Unknown column types use native units and are not combined with identified measurement types. The y-axis never extends below zero when all visible measurements are nonnegative; genuine negative values remain visible. At full scale, the plot retains the minimum and maximum of each display bucket. Statistics, cursor values and exported data use the original samples.
Predict temperature and pressure from mass flow measurements, optionally augmented with physics-derived information.

Training-only min–max normalization; sliding window of 8 samples, stride 1. Results averaged over three runs.
| Model | Data-driven RMSE | Physics-enhanced RMSE | Reduction |
|---|
Normalized RMSE × 10⁻³, mean ± standard deviation, from Tables III and IV of the paper. Noisy scenario uses Gaussian noise with standard deviation 0.1 on mass-flow measurements.
Please cite the associated publication when using the dataset.
@ARTICLE{niresi_pegnn,
author={Niresi, Keivan Faghih and Bissig, Hugo and Baumann, Henri and Fink, Olga},
title={Physics-Enhanced Graph Neural Networks For Soft Sensing in Industrial Internet of Things},
journal={IEEE Internet of Things Journal},
year={2024},
doi={10.1109/JIOT.2024.3434732}
}